Operating Instructions Safety Switch CES-I-AP-M-C04
12
Requirements for connection cables
Caution!
Risk of damage to equipment or malfunctions as a result of incorrect connec-
tion cables.
Ì Use connection components and connection cables from EUCHNER
Ì On the usage of other connection components, the requirements in the fol-
lowing table apply. EUCHNER provides no warranty for safe function in case
of failure to comply with these requirements.
Ì The connection cable must not be longer than 180 m in total.
Observe the following requirements with respect to the connection cables:
Parameter Value Unit
Conductor cross-section 0.14 ... 0.34 mm²
R max. 150 W/km
C max. 120 nF/km
L max. 0.65 mH/km
Recommended cable type LIYY 5x0.34 mm²