INSTRUCTION SHEET
AS-Interface Safety at Work Slave
ES-XW Series
This product is an emergency stop switch compatible with AS-Interface Safety at Work. Before
installing, wiring, operating and performing maintenance and inspection of this product, please read
this instruction sheet carefully to use this product correctly.
After reading, keep this instruction sheet handy. Please take care to deliver this instruction sheet to
the end user.
Note that handling this product requires expert knowledge about electricity.
SAFETY NOTE
This product is manufactured under our tightly controlled production environment. In this
instruction sheet, the dangers expected to occur due to improper handling are described under
the classifications of "Warning" and "Caution." Meanings of the terms are as follows:
Warning notices are used to emphasize that improper operation may cause severe personal
injury or death.
Caution notices are used where inattention might cause personal injury or damage to equipment.
Before using this product, read the manuals for AS-Interface safety
monitor (hereinafter referred to as “safety monitor”) and the safety
monitor setting software carefully. These manuals provide information
about installation, setup, operation, and maintenance of this product.
Be sure to turn off the AS-Interface power supply before installation,
removal, wiring, maintenance or operation of the product. Otherwise it
may cause an electric shock or a fire.
Operations other than those described in this instruction sheet can cause
damage to this product or a connected system, preventing demonstration
of the functions to their full capacities. Do not modify product since a
modified product is not guaranteed. Use this product according to the
safety standard and related laws and regulations.
Using this product for purposes different from those specified may cause
danger to an operator or damage to the system itself. Installation of this
product must be conducted by trained personal, following the instructions
in this instruction sheet. When using this product as a slave in a safety
related application, be sure to use it in combination with an AS-Interface
product having an appropriate safety monitor according to regulations and
standards. Refer to the operation manual for your safety monitor and the
chapter on connection examples in this instruction sheet. Also, check all
safety functions including safety-related equipment before the normal
operation.
Perform a functional test on this product at least once a year. Do not
disassemble, repair, or modify this product. Otherwise, the primary
safety features of this product may be lost.
1
Application
This product is an emergency stop switch authorized by TÜV Rheinland according to
IEC60947-5-5 compatible with the AS-Interface Safety at Work. When used in combination with
the safety monitor that is programmed appropriately, this switch operates as an emergency stop
switch applicable to safety category 4 in compliance with EN954-1 and IEC61508 SIL3. For this
purpose, this product generates 8x4-bit code tables defined specifically for the product, and is
scanned in each AS-Interface bus cycle by an AS-Interface master. At the same time, the data is
checked by the safety monitor. The safety loop consists of this product, the safety monitor, and
an actuator connected with the safety monitor.
2
Laws and Regulations
Standards Organization
IEC61508 Part1-7 : 2000 EN954-1 : 1996
EN62061 : 2005 IEC60947-5-5: 1997
EN60204-1 : 2005 EN50295 : 1999
EN61000-6-2 : 2005 EN61000-6-4 : 1997
NFPA79: 2002
TÜV Rheinland
UL508 CSA C22.2 No, 14 UL/ c-UL
3
Probability of Failure on Demand (PFD) and Probability
of Failure per Hour (PFH)
This product has the following Probability of Failure on Demand (PFD) and Probability of Failure
per Hour (PFH). In order to satisfy SIL requirements, calculation of PFD and PFH is needed for
the all devices comprising the complete system.
PFD 4.38 x 10
-5
PFH 1.00 x 10
-9
4
Specifications
Electrical specifications
Rated operating voltage Ue 26.5 to 31.6 V (from AS-Interface line)
Rated operating current Ie (when Ue = 30.5V)
< 25mA Non-illuminated
< 40mA
Illuminated
Input specifications
Number of inputs
2 channel inputs
(positive opening mechanism)
Output specifications
Number of output points/specifications
1 / Illuminating red LED
(only illuminated slave)
AS-Interface Specification
Slave type Safety slave
Maximum network length 100 meters in total
Maximum number of slaves in the network
31 (When any safety slaves are
connected)
Profile
(I/O . ID . ID2)
S-0.B.E (Non-illuminated)
S-7.B.E (Illuminated)
When emergency
switch is pressed.
DI0 DI1 DI2 DI3
0 0 0 0
Input
When emergency
switch is released
DI0 DI1 DI2 DI3
X X X X
X: 0,1 (Indefinite)
Data bit
Output DO1 to DO3 unused
DO0 = 1 LED ON
DO0 = 0 LED OFF
Parameter bit Not used
Environment
Operating temperature -25 to 55°C(no freezing)
Storage temperature -40 to 70°C(no freezing)
Operating humidity 45 to 85% RH (no condensation)
Structural specifications
Push lock: 32 N
Pull reset: 21 N
Operating force
Turn rest: 0.27 N·m
Minimum operating force of direct break 80 N
Minimum operating distance
for direct circuit breaking
4.0 mm
Maximum operating distance 4.5 mm
Insulation resistance 100 M or higher (500 VDC mega)
Pollution degree
3(operator unit)
[1]
2(AS-Interface communication unit)
Impact resistance
Normal operation: 15G, 11ms
Not destroyed: 100G
Vibration Resistance
Operating extremes: 10 to 500Hz,
amplitude 0.35mm, acceleration 50m/s
2
,
2 hours per axis on each of XYZ axes
Life
Mechanical / Electrical:
250,000 operations minimum
Protective structure
IP65 (operator unit)
IP20 (AS-Interface communication unit)
Recommended tightening torque
for locking ring
2.0 N·m
Weight Ø40 type: 60 g
Applicable cable UL2468AIN-F20 AWG×2C
[1] For UL and c-UL , pollution degree is 2.
5
Reset Operation
This product is a push-locking, pull- or turn-resetting emergency stop switch. When the button is
pressed, the pressed button is locked. The button is reset by pulling or turning.
Pull reset
Turn reset
Do not expose the switch to excessive shock and vibration, otherwise
the switch may be deformed or damaged, causing malfunction or
operation failure.
6
Pin Assign
IDC
Connector Body
1: AS-i – (Cable color: blue) 2: AS-i + (Cable color: brown)
Use the end connector when installing at the end of the cable.
7
Dimensions
Operator uni
t
AS-Interface communication unit
AS-Interface communication connector
Addressing port
8
Mounting Hole Layout
Operator unit X axis Y axis
Ø40 Min 50mm Min 50mm
To set an address while mounting this product on the panel, more than
60mm space is necessary on the left side in terms of the AS-Interface
communication unit. Note that adequate space cannot be allocated by
the distance specified with minimum mounting pitch. If adequate space
cannot be allocated, set the address before installing the product on the
panel or set the address after removing the AS-Interface
communication unit from the operator.
60.0
Programming cable
9
Installation
-Removing the AS-Interface communication unit
First unlock the operator button. Grab the bayonet ring (1) and pull back the bayonet ring until the
latch pin clicks (2), then turn the AS-Interface communication unit counterclockwise and pull out
(3)
(1) Grab
(2) Pull
Bayonet ring
(1) Grab
(3) Turn counterclockwise
Notes for removing the AS-Interface communication unit
(1)
While removing the AS-Interface communication unit, do not exert
excessive force, otherwise the switch may be damaged.
(2) An LED lamp is built into the AS-Interface communication unit for
illuminated pushbuttons. When removing the AS-Interface communication
unit, pull the AS-Interface communication unit straight to prevent damage to
the LED lamp. If excessive force is exerted, the LED lamp may be damaged
and fail to light.
- Panel Mounting
Remove the locking ring from the operator and check that the rubber gasket is in place. Insert the
operator from panel front into the panel hole. Face the side without thread on the operator with
TOP marking upward, and tighten the locking ring using ring wrench to a torque of 2.0 N·m
maximum.
Operator without thread
Operator without thread
TOP Marking
Rubber gasket
Locking ring
Notes for panel mounting
The panel thickness should be within the range from 0.8 to 6.0 mm.
To prevent the ES-XW emergency stop switch from rotating when resetting from the latched
position, use of an anti-rotation ring or a nameplate is recommended.
-Installing the AS-Interface communication unit
First unlock the operator button. Align the small marking on the edge of the operator with the
small marking on the yellow bayonet ring. Hold the AS-Interface communication unit, not the
bayonet ring. Press the AS-Interface communication unit onto the operator and turn the
AS-Interface communication unit clockwise until the bayonet ring clicks.
Mark
Mark
Push
Turn clockwise
Notes for installing the AS-Interface communication unit
Make sure that the bayonet ring is in the locked position. Check that the
two projections on the bayonet ring are securely in place.
Projection
Unlatched
Latched
Mounting hole dimension
10
Addressing
Turn off the power and then remove the lid of the address setting section. Connect the
programming cable to the address setting device and insert the device in the address setting
section. Then specify the address settings according to the setting procedures. After specifying
settings, be sure to replace the lid of the address setting section. Specifying address settings on
an AS-Interface slave is also possible using an AS-Interface master. Refer to the manual for the
AS-Interface master for details. Setting addresses 1 through 31 is allowed. The address
specified upon shipment is "0".
·The values shown above are the minimum dimensions for
mounting with other ø22mm pushbuttons. For other control
units of different sizes and styles, determine the values
according to dimensions, operation, and wiring
convenience.
Refer to the address setting unit instruction sheet for the operation of the address setting unit.
-Connecting the programming cable for ES-XW address setting device
The lid of the address setting device on the side of the unit can be removed. Take care not to lose
the lid, which comes off completely. By removing the lid of the address setting section, you are
able to see the terminals for connecting a programming cable. Connect the programming cable
to the terminals
Lid of addressing port
A
ddressing port for connecting
t
he programing cable is under the lid
11
Wiring
For wiring of this product, mount the connector, sold separately, to compatible cable and connect
the main unit with the cable through the connector. A special tool is necessary to connect the
connector to the cable. When mounting a connector at the end of the cable, use a connector for
termination.
The network length is a maximum of 100 meters, including all wires.
However, the maximum possible length of the wires may actually be
shorter than 100 meters depending on the type of master and
composition of the slaves. Consider the lengths of cables and wiring
topology so that voltage drops in transmission lines are no higher than
3V.
Use applicable two-wire flat cables for wiring.
A maximum of 31 units can be connected to a network. Addresses need be assigned to avoid
overlaps.
This product allows connecting safety slaves with safety equipment, and normal slaves without
safety equipment at the same time. Do not connect safety related signals to a normal slave.
The AS-Interface slaves are divided into two types: A/B slaves with expanded addresses and
standard slaves without expanded addresses. If A/B slaves and standard slaves are connected
simultaneously, the maximum number of slaves connectable to a network may exceed 31.
12
Setting Safety Monitor
When using this product in combination with a safety monitor, use a “2-channel forced” monitor
device with an “emergency shutdown” icon.
2-channel forced
Emergency shutdown
EUCHNER GmbH + Co. KG Kohlhammerstraße 16 D-70771 Leinfelden-Echterdingen
Tel. +49/711/75 97-0 Fax +49/711/75 33 16 www.euchner.de info@euchner.de
1 2
1
2
Subject to technical modifications; no responsibility is accepted for the accuracy of this information. © EUCHNER GmbH + Co. KG 105187-02-04/09
Vue de la page 0
1

Résumé du contenu

Page 1 - INSTRUCTION SHEET

INSTRUCTION SHEET AS-Interface Safety at Work Slave ES-XW Series This product is an emergency stop switch compatible with AS-Interface Safety at Wo

Commentaires sur ces manuels

Pas de commentaire