Euchner MGB (V1.2.3) Manuel d'utilisateur Page 9

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 12
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 8
MGB Help for Setup and Service
2.7 Separate operation functions on the safety relay, but not series
operation
Fault symptom:
The connection of a separate MGB operation to a safety relay functions, but the connection in series operation
to a safety relay does not function despite correct wiring. The safety relay displays a fault or does not switch on.
Possible fault causes:
The first MGB is connected to the safety relay with its inputs I
A
and I
B
, and the current that the safety relay
can supply is insufficient.
Remedy:
Wiring of the first inputs I
A
und I
B
directly to the 24 V DC power supply.
115387-01-04/12 Subject to technical modifications Page 9/12