AS-i 3.0 Command Interface Command Interface Examples
Subject to reasonable modifications due to technical advances Id.-No.: 102875 Issue date - 3.12.2007 EUCHNER GmbH + Co. KG
Kohlhammerstraße 16, D-70771 Leinfelden-Echterdingen Tel. +49/711/7597-0, Fax +49/711/753316
81
No result because toggle bit = 0.
Set the toggle bit:
The master is now in configuration mode.
Result: See chapter 4 "Commands of the Command Interface".
2. Write single configuration to master
Writing a configuration of an AS-i slave to the master.
For example:
16 bit input 4 CH at address 4 (Slave data sheet)
ID: 3
hex
ID2: E
hex
IO: 7
hex
ID1: F
hex
Response
Byte 1 00
hex
(or old values)
Byte 2 00
hex
(or old values)
Byte 3 00
hex
(or old values)
Byte 4 00
hex
(or old values)
……
Byte 12 00
hex
(or old values)
Request: SET_OP_MODE
Byte 1 0C
hex
(SET_OP_MODE)
Byte 2 80
hex
(T = 1, master 1, single master)
Byte 3 01
hex
(= config mode)
Byte 4 00
hex
……
Byte 12 00
hex
Response
Byte 1 0C
hex
Byte 2 80
hex
(T = 1, result = 0)
Byte 3 00
hex
(or old values)
Byte 4 00
hex
(or old values)
……
Byte 12 00
hex
(or old values)